1 /
1
Huber + Suhner RADOX® 125
Description:
Key Specifications
Maximum permitted operating temperatur of the conductor EN50565/IEC 60092
+90°CShort circuit temperatur rating of the conductor EN50565/IEC 60092
+250°CTEMPERATURE RANGE
-40 to +125°CMinimum bending radius
Outer diameter ≤ 12mm: 3 x DOuter diameter > 12mm: 4 x D
Category
Features
01
General Properties
- Electron beam crosslinked Isolation;
- excellent high temperature, low temperature, ozone, weathering and abrasion resistance
- small amount of smoke
- halogen free
- flamm-retardant
- soldering iron resistant
- easy to strip and process
- flexible
02
APPLICATION
For protected and fixed installation inside electrical equipment, especially suitable for the connection of motor windings, switchboards, magnets and transformers.
Standard
In conformity with | Standard | |
---|---|---|
Fire protection in ships 1- 300 mm2 | Fulfilled | IEC 60092 |
Vertical flame spread of a single cable Vertical flame spread of bunched cables Smoke density Corrosivity of combustion gases Amount of halogen acid gas |
50 L < 540 mm L <2.5 m T > 60 % pH > 4.3, C < 10 mS/mm HCI+HBr <0.5% |
IEC 60332- 1- 2 IEC 60332- 3- 22 IEC 61034- 2 IEC 60754- 2 IEC 60754- 1 |
Fire protection on railway vehicles, hazard level | HL1 - HL3 | EN 45545 |
Vertical flame spread Vertical flame spread, bunched, D < 6mm Vertical flame spread, bunched, 6 < D < 12 mm Vertical flame spread, bunched, D > 12 mm Smoke density Toxicity |
50 < L < 540 mm L < 1.5 m L < 2.5 m L < 2.5 m T > 70 % ITC < 6 |
EN 60332- 1- 2 EN 50305, 9.1.2 EN 50305, 9.1.1 EN 60332- 3- 24 EN 61034- 2 EN 50305, 9.2 |
Fire protection on building products , hazard level | ||
Cross- section 0.5 - 6 mm2 Flame Spread Cross- section 10 - 300 mm2 Flame Spread Flame Spread |
Eca H ≤ 425 mm B2ca - s1a, d2, a1 H ≤ 425 mm FS ≤ 1.5 m |
EN 13501- 6 EN 60332- 1- 2 EN 13501- 6 EN 60332- 1- 2 EN 50399 |
SLIDE TO VIEW MORE